https://cdn.prod.website-files.com/6a838ff6d7b603ad9aeaed44/6ac8509bc45e1386e0e39969_wafr_frdge_on_demand_cooling_v3.mp4

Products & Solutions

Thermal equipment

FRDGE

Wafr Technology

Under Development

FRDGE

Thermal infrastructure for high-density computing and liquid-cooled environments.

Category

Thermal equipment

Application

High-density, liquid-cooled deployment

Support

Selection, documentation and delivery coordination

Thermal equipment

Wafr role: proprietary thermal equipment, application support and project-specific coordination.

Overview

Capabilities

FRDGE is both a cooling system and a thermal battery. It uses lower ambient temperatures to cool a facility while storing cooling for later use, helping reduce the amount of mechanical cooling required. Low-ambient operation, in climates with sufficiently low outdoor night time temperatures, FRDGE can use ambient conditions for heat rejection while charging its thermal storage. In the right climate and system configuration, this can significantly reduce or eliminate the need for mechanical chillers.

High-ambient operation, in hotter climates, FRDGE can shift chiller operation to cooler nighttime hours, when chillers operate more efficiently. Stored cooling can then be dispatched during the hottest parts of the day, reducing peak cooling demand and overall energy use. System impact: Depending on climate, FRDGE can reduce cooling energy requirements by 30 to 80% and water consumption by up to 95%.

THERMAL CAPACITY

Custom engineered to project requirements

COOLING + STORAGE

Integrated in one system

Wafr FRDGE cooling and thermal storage unit: white container with top-mounted fans, finned coils and a control panel

https://cdn.prod.website-files.com/6a838ff6d7b603ad9aeaed44/6ac954a8e856ce496fd78c03_wafr_frdge_hero_v4.mp4

Engineering

Technical specifications

General product scope

Structured so engineering and procurement teams can review key ranges quickly.

Architecture

Modular

Redundancy

Configurable

Fluid loop

Application specific

Controls

Integrated

Deployment

Packaged / field integrated

Applications

Facility cooling loop

Interface

Facility cooling loop

Select type
▾

Liquid-Filled Distribution

oil-immersed

transformers

Fluid Coolers

fluid-coolers

dry-coolers

WTB Commercial

wtb-commercial

thermal-storage-battery

Three-Phase Pad-Mounted

pad-mount

transformers

Freon Condensers

freon-condensers

dry-coolers

Single-Phase Pole-Mounted

pole-mounted

transformers

Ammonia Condensers

ammonia-condensers

dry-coolers

Dry-Type & Cast-Coil

dry-type

transformers

CO2 Gas Coolers

gas-coolers

dry-coolers

Oil Coolers

oil-coolers

dry-coolers

Medium & Large Power

power-transformers

transformers

45–3,000 kVA

4.16–34.5 kV / 600Y/347–208Y/120 V

Delta–Wye grounded

ONAN

CSA C802.1 / IEEE C57.12.00

oil-immersed

15–7,500 kVA

Up to 35 kV / 600Y/347–208Y/120 V

—

AN / AF

CSA C9 / CAN/CSA C802.2

dry-type

10–167 kVA

7.2 / 7.62 / 14.4 / 19.9 kV / 120/240 V

Single-phase

ONAN

CSA C227 series

pole-mounted

750 kVA

12.47 kV / 600Y/347 V

—

ONAN

CSA C227.4 / IEEE C57.12.34

pad-mount

470–2,190 kW

Water / Glycol

1.8–3.2 mm

20 ft (6,058 mm) / 40 ft (12,192 mm)

AC / EC / marine / explosion-proof

fluid-coolers

343–2,005 kW

R404A

1.8–3.2 mm

20 ft (6,058 mm) / 40 ft (12,192 mm)

AC / EC / marine / explosion-proof

freon-condensers

420–2,237 kW

NH3

1.8–3.2 mm

20 ft (6,058 mm) / 40 ft (12,192 mm)

AC / EC / marine / explosion-proof

ammonia-condensers

407–1,267 kW

CO2 (94 Bar)

1.8–3.2 mm

20 ft (6,058 mm) / 40 ft (12,192 mm)

AC / EC / marine / explosion-proof

gas-coolers

240–1,309 kW

ISO VG 46 oil

1.8–3.2 mm

20 ft (6,058 mm) / 40 ft (12,192 mm)

AC / EC / marine / explosion-proof

oil-coolers

Maximum nominal cold storage capacity

kWh(th)

1,500

1,000

500

wtb-commercial

3–200+ MVA

69 kV / 25 kV

Project specific

ONAN / ONAF / OFAF / ODAF

CSA C88 / IEEE C57

power-transformers

1,000 kVA

13.8 kV / 600Y/347 V

—

ONAN

CSA C227.4 / IEEE C57.12.34

pad-mount

3–200+ MVA

69 kV / 13.8 kV

Project specific

ONAN / ONAF / OFAF / ODAF

CSA C88 / IEEE C57

power-transformers

Phase-change temperature

°C

Grade C7: 7.5 ± 1 · Grade C18: 18 ± 1

Grade C7: 7.5 ± 1 · Grade C18: 18 ± 1

Grade C7: 7.5 ± 1 · Grade C18: 18 ± 1

wtb-commercial

1,500 kVA

13.8 kV / 600Y/347 V

—

ONAN

CSA C227.4 / IEEE C57.12.34

pad-mount

3–200+ MVA

115 kV / 34.5 kV

Project specific

ONAN / ONAF / OFAF / ODAF

CSA C88 / IEEE C57

power-transformers

Charging water inlet temperature

°C

C7: 5 · C18: 15

C7: 5 · C18: 15

C7: 5 · C18: 15

wtb-commercial

2,000 kVA

24.9 kV / 600Y/347 V

—

ONAN

CSA C227.4 / IEEE C57.12.34

pad-mount

3–200+ MVA

115 kV / 13.8 kV

Project specific

ONAN / ONAF / OFAF / ODAF

CSA C88 / IEEE C57

power-transformers

Discharge outlet temperature

°C

C7: 7–12 · C18: 18–23

C7: 7–12 · C18: 18–23

C7: 7–12 · C18: 18–23

wtb-commercial

2,500 kVA

24.9 kV / 600Y/347 V

—

ONAN

CSA C227.4 / IEEE C57.12.34

pad-mount

3–200+ MVA

138 kV / 34.5 kV

Project specific

ONAN / ONAF / OFAF / ODAF

CSA C88 / IEEE C57

power-transformers

Peak discharge temperature

°C

C7: 16.8 · C18: per test report

C7: 16.8 · C18: per test report

C7: 16.8 · C18: per test report

wtb-commercial

3,000 kVA

34.5 kV / 600Y/347 V

—

ONAN

CSA C227.4 / IEEE C57.12.34

pad-mount

3–200+ MVA

138 kV / 25 kV

Project specific

ONAN / ONAF / OFAF / ODAF

CSA C88 / IEEE C57

power-transformers

Storage method

—

Latent (phase change)

Latent (phase change)

Latent (phase change)

wtb-commercial

Up to 10 MVA

Project specific

—

ONAN

CSA C227.4 / IEEE C57.12.34

pad-mount

3–200+ MVA

230 kV / 34.5 kV

Project specific

ONAN / ONAF / OFAF / ODAF

CSA C88 / IEEE C57

power-transformers

Rated flow rate

m³/h

58

40

20

wtb-commercial

Water supply pipe diameter

DN

150

150

100

wtb-commercial

Working pressure

MPa

0.8–1.0

0.8–1.0

0.8–1.0

wtb-commercial

Pressure drop

kPa

76.8

65.7

50.7

wtb-commercial

Recommended pipe velocity

m/s

0.8

0.8

0.8

wtb-commercial

Recommended chiller capacity

kW

Per configuration

142–165

70–80

wtb-commercial

Recommended charging window

h

≈ 8 (off-peak / valley tariff)

≈ 8 (off-peak / valley tariff)

≈ 8 (off-peak / valley tariff)

wtb-commercial

Recommended discharge window

—

Local peak tariff hours

Local peak tariff hours

Local peak tariff hours

wtb-commercial

Control

—

Networked automatic program control

Networked automatic program control

Networked automatic program control

wtb-commercial

Unit size (L × W × H)

mm

9,300 × 2,896 × 3,170

6,800 × 2,896 × 3,170

3,808 × 2,896 × 3,170

wtb-commercial

Operating weight

kg

≥ 36,000

≥ 26,500

≥ 14,300

wtb-commercial

Wafr FRDGE cooling and thermal storage unit: white container with top-mounted fans, finned coils and a control panel

Engineering notes

Operating temperatures, flow requirements and control logic are engineered around each project's cooling load, climate and site conditions.

FRDGE can integrate with existing or new cooling infrastructure, including liquid cooling loops, direct-to-chip systems and immersion cooling where required.

Redundancy, controls and operating strategy are configured around project-specific reliability and performance requirements.

Deployment options include modular packaged systems and field-integrated installations, allowing FRDGE to scale with the cooling requirements of the site.

Compliance

Standards & certifications

CSA

Applicable by configuration

UL / cUL

Applicable by configuration

IEEE

Applicable by configuration

ANSI

Applicable by configuration

NEMA

Applicable by configuration

QA Docs

Applicable by configuration

Quality Commitment

Warranty & After-Sales Support

24 months warranty against manufacturing defects, counted from commissioning (or 30 months from shipment, whichever ends first)

Covers transformer core, windings, tank and factory-installed components

Defective units repaired or replaced at Wafr's cost, including freight

Technical support: remote diagnosis within 48 hours, on-site service available for major claims

Spare parts shipped within 30 days for standard models

Extended warranty and preventive-maintenance packages available on request

Final warranty terms per purchase contract.

Resources

Technical resources

Everything an engineer or procurement team needs to move from evaluation to specification.

Brochure

FRDGE Brochure

Downloadable project and product documentation.

Download ↓

Datasheet

Technical Datasheet

Downloadable project and product documentation.

Download ↓

Technical File

System Architecture

Downloadable project and product documentation.

Download ↓

Technical File

Integration Guide

Downloadable project and product documentation.

Download ↓

Specify

FRDGE

for your project

Send Wafr your project requirements and the team can confirm fit, configuration and documentation.

Request a Quote
Let's connect

Talk to Our Team

Start with a simple general inquiry to start the conversation. Or tell Wafr what equipment you need, where it is going and when the project needs it.